100kV ~ 400kV Range
HCTT 350kV/50kVA Test Transformer
Home > Systems > AC Dielectric Test > AC Test Transformer > 100kV ~ 400kV Range

HCTT 350kV/50kVA Test Transformer

Lead time: 90 days

Mode: HCTT 350KV/50KVA
Cylinder type                                                                                   Rated input current: 125A
Single phase                                                                                     Rated output current: 0.143A
Frequency: 50Hz                                                                             Cooling methods: ONAN
Rated Capacity: 50kVA                                                                   No-load current ≤10%
Rated input voltage: 0.4kV                                                            Waveform deviation ≤5%
Rated output voltage: 350kV                                                         Impedance voltage ≤10%
PD Level: <5pC at 100%UH of complete test system

Working for 60 minutes allowed at 100% rated current & voltage;
Continuous working allowed at 80% rated current & voltage; and temperature rise of transformer winding is less than 65K, temperature rise of oil surface is less than 55K.
Dimension: Dia. Ø1500*2000                                                   
Weight: <2500kg

HCTT 350kV/50kVA Test Transformer HCTT 350kV/50kVA Test Transformer

HCTT 350kV/50kVA Test Transformer HCTT 350kV/50kVA Test Transformer
Transformer Oil: 
25# transformer oil is from Karamay Refinery. The oil indicator can reach the oil level for 500KV transformers. Factory test of test transformer should use new transformer oil supplying with transformers and perform oil inspection before or after factory test. Oil inspection report should be provided when the transformer delivered filled with oil. Quality of transformer oil should meet the requirements of SH0040-91, GB2536-90, GB7595-87, SD187-86, Class II A of IEC-296 standards. Components PCB are prohibited in the oil. When doing acceptance test on-site, the oil performance should satisfy the following requirements: DGA analysis of total hydrocarbons less than 10 mg/L, the breakdown voltage of the oil should not be less than 65kV/2.5mm, dielectric loss(90°C) is not more than 0.3%, water content is not more than 10mg/L, the gas content is not more than 1%.

Principle Diagram: 

  