>400kV Range
HCTT-2×350kV /250kVA AC Test Transformer
Home > Systems > AC Dielectric Test > AC Test Transformer > >400kV Range

HCTT-2×350kV /250kVA AC Test Transformer

Mode: HCTT 2x350KV/250KVA
Cylinder type, two modules,    Single phase,   Frequency: 50Hz
Rated Capacitance:LV Capacitance: 250kVA, HV Capacitance: 700kVA
Rated Voltage:LV Voltage: 2*0.6kV; HV Voltage: 2*350kV
Rated Current:LV Current: 2*208.3A, HV Current: 0.375A
(HV terminal of the transformer will be earthed through a current transformer 5/5 so as to check the current value of HV side and ensure safety of the operators and equipment.)
Waveform deviation ≤3%           Unload Current: IO<10%
Impedance voltage ≤15%
Voltage Ratio of Measurement Winding: 2000:1
Over Current Ability: Continuous working for 300S under 125% rated current, then thermal damage or distortion of the winding shall not be occurred.
Over Voltage Ability: Over voltage at 110% UH (770kV) for 60s., then it shall not happened any insulation damage for the testing transformer.
Insulation Level:10kV/1min(low voltage terminal to earth)
Noise: ≤60dB
PD Level: <5pC at 100%UH of complete test system;
Unevenness at 2 transformer in series: ≤±5%
Transformer Oil: 25# China made
Operating Time: (starting from environment temperature)

Working for 60 minutes allowed at 100% rated current & voltage;
Continuous working allowed at 80% rated current & voltage; and temperature rise of transformer winding is less than 65K, temperature rise of oil surface is less than 55K.
Protection: The surge arrestors 3kV shall be installed among excitation winding of the transformer and transfer winding for protection purpose.
Injection and release valve for transformer oil are available.

HCTT-1000kV AC Test Transformer HCTT-1000kV AC Test Transformer

HCTT-1000kV AC Test Transformer HCTT-1000kV AC Test Transformer

Upper Stage Transformer
Mode: HCTT-125kVA/350kV-II
Cylinder type,  Single phase,  Frequency: 50Hz
Rated Capacitance: 125kVA
Rated Voltage: LV Voltage: 0.6kV, HV Voltage: 350kV
Rated Current: Exciting current: 208.3A ,HV Current: 0.375A
Impedance Voltage ≤4.5%        Waveform deviation ≤3%
Dividing Ratio of Measurement Windings:1000:1
Noise level ≤60dB (Measure in 4 meters distance)
Cooling: ONAN
Over Voltage Ability: Continuous working for 60S minutes under 110% rated voltage, then thermal damage or distortion of the winding shall not be occurred.
PD Level: <5pC at 100%UH of complete test system;

Insulation of Winding to Earth:
>2500MΩ (HV winding to LV winding to earth);
>2500MΩ (LV winding to HV winding to earth);
Insulation Level: 10kV/1min (LV winding to HV winding and transformer housing)
Insulation Level: 5kV/1min (measurement winding to LV winding, HV winding and transformer housing)

Electric Strength of Transformer Oil:
- Breakdown Voltage>60kV/2.5mm Moisture<10ppm
- Dielectric Loss<0.5%(at 90℃)
- Without acetylene in oil; Solidifying point>40

Sub-Stage Transformer
Tyoe: HCTT-250kVA/350kV-I
Single phase,  Cylinder Type,  Frequency: 50Hz
Rated Capacity: LV capacitance: 250kVA, HV Capacitance: 125kVA,Transfer capacitance: 125kVA
Rated Voltage: HV Volt.:350kV, Transfer volt: 0.6kV
Rated Current: HV Current: 0.375A,Transfer current: 208.3A
Impedance Voltage: ≤4.5%         Waveform deviation ≤3%
Dividing Ratio of Measurement Windings:1000:1
Noise level ≤60dB (Measure in 4 meter distance)
Cooling: ONAN
PD Level: <5pC at 100%UH of complete test system;
Over Voltage: Continuous working for 60S minutes under 110% rated voltage, then thermal  damage or distortion of the winding shall not be occurred.

Insulation of Winding to Earth:
>2500MΩ (HV winding to LV winding and measurement winding to earth);
>2500MΩ (LV winding to HV and measurement winding to earth);
>2500MΩ (measurement winding to HV and LV winding to earth)
Insulation Level: 10kV/1min (LV winding to HV winding and transformer housing)
Insulation Level: 5kV/1min (measurement winding to LV winding, HV winding and transformer housing)    Electric Strength of Transformer Oil:
- Breakdown Voltage>60kV/2.5mm Moisture<10ppm
- Dielectric Loss<0.5%(at 90℃)
- Without acetylene in oil; Solidifying point>40 

Principle Diagram: 
                      

  