Mode: HCTT 2x375KV/375KVA
Cylinder type Single phase
Working frequency: 50Hz
Rated capacity: 375KVA
Rated input voltage: 3KV
Rated output current: 750KV
Rated input current: 62.5*2A
Rated output current: 0.5A
Impedance voltage: ≤13%
Voltage unevenness: <±5%
Over current ability: continuous working for 2 min at 130% rated current without any damage and distortion to transformer winding;
Over voltage ability: working for 60s at 110% rated voltage without any damage to transformer insulation
Working time: continuous working for 60 min under 100% rated voltage and rated current is allowed;
Temperature rising: temperature rising of transformer winding is ≤65K, temperature rising of transformer oil is ≤55K
Protection: between lower LV winding and upper LV winding of test transformer installed 3 KV MOA.
Height: about 6400mm
Weight: 12000kg
Upper stage:
HCTT 187.5KVA/375KV
Cylinder type
Single phase
Working frequency: 50Hz
Rated capacity: 187.5KVA
Rated voltage: LV 3KV HV 375KV
Rated current: LV current: 62.5A HV current: 0.5A
Impedance voltage: ≤4.5%
Dielectric loss: <0.4%
Noise level: ≤60db
PD level: <5pC under 100% rated voltage; <3pC under 80% rated voltage
Over current ability: continuous working for 2 min at 130% rated current without any damage and distortion to transformer winding;
Over voltage ability: working for 60s at 110% rated voltage without any damage to transformer insulation, waveform distortion ≤5%;
Working time: continuous working for 60 min under 100% rated voltage and rated current is allowed;
Temperature rising: temperature rising of transformer winding is ≤65K, temperature rising of transformer oil is ≤55K
Lower Stage
HCTT 375KVA/375KV
Cylinder type
Single phase
Working frequency: 50Hz
Rated capacity: LV Capacity: 375KVA HV Capacity: 187.5KVA Total capacity: 187.5KVA
Rated voltage: LV: 3KV HV :375KV Total voltage: 3KV
Rated current: LV current: 2*62.5A HV current: 0.5A Total Current: 62.5A
Impedance voltage: ≤4.5%
Noise level: ≤60db
PD level: <5pC under 100% rated voltage; <3pC under 80% rated voltage
Over current ability: continuous working for 2 min at 110% rated current without any damage and distortion to transformer winding;
Over voltage ability: working for 60s at 110% rated voltage without any damage to transformer insulation, waveform distortion ≤5%;
Working time: continuous working for 60 min under 100% rated voltage and rated current is allowed;
Temperature rising: temperature rising of transformer winding is ≤65K, temperature rising of transformer oil is ≤55K
Oil electric strength test: Breakdown voltage ≥65kV / 2.5mm; moisture <10ppm; dissipation factor ≤0.25% (25 ℃)
Principle Diagram:
HIMALAYAL provides innovative products that comprise high voltage test equipment, full-set high voltage test instruments, on-site test systems and on-line monitoring systems, and services regarding tests, diagnostics and asset monitoring for clients in power industry. We help to ensure safety and reliability in the power generation, transmission and distribution.
Himalayal Corporation Limited
Tel:+86 21 5059 9069
Email: info@himalayal.com
http://www.himalayal.com
http://www.himalayal.com.cn