HTTS 10KV/200KVA Tank type Test Transformer
Home > Systems > AC Dielectric Test > AC Test Transformer > ≤100kV Range

HTTS 10KV/200KVA Tank type Test Transformer

Lead time: 45 days

Mode: HTTS 10KV/200KVA
Tank type                                                     
Rated Capacity: 200kVA
Single phase                                                 
Rated Voltage: Input voltage: 0.6kV  (Can be customized according to User's feeding power) ;
Output voltage: 10kV
Frequency:50Hz  / 60Hz                                         
Rated Current: Input current : 333.3A;
Output Current:20A
(HV terminal of the transformer will be earthed through a current transformer 5/5 so as to check the current value of HV side and ensure safety of the operators and equipment)
Waveform deviation ≤3%                            
Non-load Current: IO<10%
Impedance voltage ≤10%                            
Voltage Ratio of Measurement Winding:1000:1

Over Current Ability: Continuous working for 3 minutes under 120% rated current, then thermal damage or distortion of the winding shall not be occurred.
Over Voltage Ability: Over voltage at 110% UH (11kV) for 60s., then it shall not happened any insulation damage for the testing transformer.
Insulation Level:18kV/1min(low voltage terminal to earth)           
Transformer Oil:25# China made
Noise:≤60dB                                                                                           
Dielectric loss: less than 0.5%.
PD Level: <5pC at rated voltage (10kV)                                             
One hour on and one hour off at 100% rated current & voltage;Continuous working allowed at 80% rated current & voltage; and temperature rise of transformer winding is less than 65K, temperature rise of oil surface is less than 55K.

HTTS 10KV/200KVA Tank type Test Transformer HTTS 10KV/200KVA Tank type Test Transformer

HTTS 10KV/200KVA Tank type Test Transformer HTTS 10KV/200KVA Tank type Test Transformer

Transformer Oil:
25# transformer oil is from Karamay Refinery. The oil indicator can reach the oil level for 500KV transformers. Factory test of test transformer should use new transformer oil supplying with transformers and perform oil inspection before or after factory test. Oil inspection report should be provided when the transformer delivered filled with oil. Quality of transformer oil should meet the requirements of SH0040-91, GB2536-90, GB7595-87, SD187-86, Class II A of IEC-296 standards. Components PCB are prohibited in the oil. When doing acceptance test on-site, the oil performance should satisfy the following requirements: DGA analysis of total hydrocarbons less than 10 mg/L, the breakdown voltage of the oil should not be less than 65kV/2.5mm, dielectric loss (90°C) is not more than 0.3%, water content is not more than 10mg /L, the gas content is not more than 1%.

Principle Diagram: 

  
Where To Buy

Related Photos

Related Products