>1600KV Range
HIVG 2400KV-120KJ Impulse Voltage Generator
Home > Systems > Impulse Generator > Impulse Generator > >1600KV Range

HIVG 2400KV-120KJ Impulse Voltage Generator

Lead time: 120 days

Mode: HIVG 2400KV-120KJ

Related Standards: 
* IEC 60060-1-2010 High-voltage test techniques - Part 1: General definitions and test requirements
* IEC 60060-2-2010 High-voltage test techniques. Part 2: Measuring systems
* IEC 61083-1-2001 Instruments and software used for measurement in high-voltage impulse tests - Part 1: Requirements for instruments
* IEC 61083-2-1996 Digital recorders for measurements in high-voltage tests - Part 2: Evaluation of software
* ANSI/IEEE 4a-2001 Techniques of High-Voltage Testing
* ANSI/IEEE 376-1975 Measurement of Impulse Strength and Impulse Bandwidth
* ANSI/IEEE 1122-2007 Digit Recorders for Measurements in High-Voltage Impulse Tests
* ASTM D69-D2484 Electrical Insulation ()
* ASTM D2518-Latest Electrical Insulation (
)

Technical Parameters: 
1) Rated Voltage:±2400kV
2) Rated stage voltage:±200kV
3) Rated charging voltage:±200kV
4) Rated energy:120kJ                       
5) Each stage impulse capacitor: 0.5μF/200kV
6) Stages:12 stages
7) Stage energy:10kJ
8) Impulse voltage waveform parameter:
     a) Standard lightning impulse voltage full-wave: 1.2±30%ms /50±20%ms,
          Amplitude: ±3%, oscillation at peak value less than 5% of amplitude
      b) Standard switching impulse wave: 250±20%ms /2500±60%ms
      c) Standard lightning chopping wave: 2-5us.
      d) This two impulse voltage waveform parameter and deviation meet the requirement of GB311 and GB16927.
9) Minimum output voltage efficiency
     Standard lightning impulse voltage full-wave≥90% (No test object)Standard switching impulse wave≥70% (test object capacitance is 1000pF)
10) Synchronous range: stage voltage is between 10%~100% of rated voltage.
       Positive and negative polarity synchronous range: less than 20%.
11) Synchronous discharge out of control rate <2% (Within the range: 10%~100% of rated voltage )
12) Sparking range: 10%-100%Un
13) Minimum output voltage: ≥10% rated voltage.
14) Charging voltage instability <±1.0%
15) Deviation between charging voltage and reference voltage  <±1.0%
16) Working time:
       When voltage above than 70% rated voltage, the systems can continuous working each 120s (charging and discharging).
       When the voltage is below 70% of rated voltage, the system the system can continuous working (charging and discharging).
17)Under Maximum charging voltage, minimum discharge time not less than 60s.


Principle Diagram: 
Principle diagram