Mode: HIVG 2800KV-420KJ
Related Standards:
* IEC 60060-1-2010 High-voltage test techniques - Part 1: General definitions and test requirements
* IEC 60060-2-2010 High-voltage test techniques. Part 2: Measuring systems
* IEC 61083-1-2001 Instruments and software used for measurement in high-voltage impulse tests - Part 1: Requirements for instruments
* IEC 61083-2-1996 Digital recorders for measurements in high-voltage tests - Part 2: Evaluation of software
* ANSI/IEEE 4a-2001 Techniques of High-Voltage Testing
* ANSI/IEEE 376-1975 Measurement of Impulse Strength and Impulse Bandwidth
* ANSI/IEEE 1122-2007 Digit Recorders for Measurements in High-Voltage Impulse Tests
* ASTM D69-D2484 Electrical Insulation (Ⅰ)
* ASTM D2518-Latest Electrical Insulation (Ⅱ)
Technical Parameters:
1) Rated Voltage: ±2800kV
2) Rated stage voltage: ±200kV
3) Rated charging voltage: ±100kV
4) Rated energy: 420kJ
5) Rated impulse capacity 0.125uF (Single impulse capacity is 3uF/100KV, 28 in total)
6) Stages: 14 stages
7) Rated stage capacity/ stage voltage/ stage energy: 1.5Uf
8) Stage energy: 30KJ
9) Minimum output voltage: >10%UH
10) Charging voltage instability: <±1.0%
11) Synchronous range: ≥20%
12) Synchronous discharge out of control rate <2%
13)Sparking range: 10%-100%UH
14) Impulse voltage waveform parameter:
a) Standard lightning impulse wave:1.2±30%ms /50±20%ms; Oscillation at the peak amplitude is ≤ 5%.
b) Standard switching impulse wave: 250±20%ms /2500±60%ms
c) Standard lightning impulse chopping wave: Chopping time: 2-6us, chopping time standard deviation: <± 0.2μS
These three impulse voltage waveform parameter and deviation meet the requirement of standards GB311 and GB16927 about the impulse voltage and impulse current waveform parameters.
15) Voltage utilization factor:
Lightning impulse voltage full-wave
When positive and negative lightning out-of wave no-load output, the voltage utilization factor is ≥90
Switching impulse voltage full-wave:
When positive and negative lightning out-of wave load is 3000pF, the voltage utilization factor is ≥65%
16) Working time:
When voltage above than 70% rated voltage, the systems can continuously working each 120s.
When the voltage is below 70% of rated voltage, the system the system can continuous working each 90s.
17) Height of the generator: 10550mm
18) Weight of the generator: 11200kg
Principle Diagram:
HIMALAYAL provides innovative products that comprise high voltage test equipment, full-set high voltage test instruments, on-site test systems and on-line monitoring systems, and services regarding tests, diagnostics and asset monitoring for clients in power industry. We help to ensure safety and reliability in the power generation, transmission and distribution.
Himalayal Corporation Limited
Tel:+86 21 5059 9069
Email: info@himalayal.com
http://www.himalayal.com
http://www.himalayal.com.cn