>1600KV Range
HIVG 3600KV-360KJ Impulse Voltage Generator
Home > Systems > Impulse Generator > Impulse Generator > >1600KV Range

HIVG 3600KV-360KJ Impulse Voltage Generator

Lead time: 120 days

Mode: HIVG 3600KV-360KJ

Related Standards: 
* IEC 60060-1-2010 High-voltage test techniques - Part 1: General definitions and test requirements
* IEC 60060-2-2010 High-voltage test techniques. Part 2: Measuring systems
* IEC 61083-1-2001 Instruments and software used for measurement in high-voltage impulse tests - Part 1: Requirements for instruments
* IEC 61083-2-1996 Digital recorders for measurements in high-voltage tests - Part 2: Evaluation of software
* ANSI/IEEE 4a-2001 Techniques of High-Voltage Testing
* ANSI/IEEE 376-1975 Measurement of Impulse Strength and Impulse Bandwidth
* ANSI/IEEE 1122-2007 Digit Recorders for Measurements in High-Voltage Impulse Tests
* ASTM D69-D2484 Electrical Insulation ()
* ASTM D2518-Latest Electrical Insulation (
)

Technical Parameters: 
1) Rated Voltage: ±3600kV
2) Rated stage voltage: ±200kV
3) Rated charging voltage: ±100kV
4) Rated energy: 360kJ
5) System overall capacity: 0.05555μF (2uF/100kV per pulse capacitor, overall 36units.)
6) Stages: 18 stages
7) Stage energy: 30kJ
8) Impulse voltage waveform parameter:
     a) Standard lightning impulse voltage full‐wave:
          (≤4nF) 1.2±30%μs /50±20%μs;
          (>4nF) 1~5μs/40~60μs
          Amplitude: oscillation at peak value less than 5% of amplitude
     b) Standard switching impulse wave: 250±20%μs /2500±60%μs
     c) Standard lightning impulse chopping wave: Standard chopped time: 2~6us;
     d) This two impulse voltage waveform parameter and deviation meet the requirement of GB311 and GB16927.
9) Minimum output voltage efficiency
    Standard lightning impulse voltage full‐wave≥90% (No test object)
    Standard lightning impulse voltage full‐wave≥85% (test object capacitance is 3000pF)
    Standard switching impulse wave≥70% (test object capacitance is 3000pF)
10) Synchronous range: stage voltage is between 20%~100% of rated voltage.
11) Synchronous discharge out of control rate <2% (Within the range: 10%~100% of rated voltage )
12) Sparking range: 15%‐100%Un
13) Minimum output voltage: ≥15% rated voltage.
14) Charging voltage instability <±1.0%
15) Deviation between charging voltage and reference voltage <±1.0%
16) Working time: 
       When voltage above than 70% rated voltage, the systems can continuousworking each 120s (charging and discharging). 
       When the voltage is below 70% of rated voltage, the system the system can continuous working each 90s (charging and discharging).
17) Generator overall height: 13200mm
18) Generator overall weight: 10280kg