≤800kV Range
HIVG 600KV-5KJ Impulse Voltage Generator
Home > Systems > Impulse Generator > Impulse Generator > ≤800kV Range

HIVG 600KV-5KJ Impulse Voltage Generator

Lead time: 60 days

Mode: HIVG 600KV-5KJ

Related Standards: 
* IEC 60060-1-2010 High-voltage test techniques - Part 1: General definitions and test requirements
* IEC 60060-2-2010 High-voltage test techniques. Part 2: Measuring systems
* IEC 61083-1-2001 Instruments and software used for measurement in high-voltage impulse tests - Part 1: Requirements for instruments
* IEC 61083-2-1996 Digital recorders for measurements in high-voltage tests - Part 2: Evaluation of software
* ANSI/IEEE 4a-2001 Techniques of High-Voltage Testing
* ANSI/IEEE 376-1975 Measurement of Impulse Strength and Impulse Bandwidth
* ANSI/IEEE 1122-2007 Digit Recorders for Measurements in High-Voltage Impulse Tests
* ASTM D69-D2484 Electrical Insulation (Ⅰ)
* ASTM D2518-Latest Electrical Insulation (Ⅱ)

HIVG 600KV-5KJ Impulse Voltage Generator HIVG 600KV-5KJ Impulse Voltage Generator

HIVG 600KV-5KJ Impulse Voltage Generator HIVG 600KV-5KJ Impulse Voltage Generator

Technical Parameters: 
1) Rated Voltage: ±600kV (Can be upgrade to 900kV 7.5kJ)
2) Rated stage voltage: ±100kV
3) Rated charging voltage: ±100kV
4) Rated energy: 5kJ
5) Each stage impulse capacitor: 0.166μF/100kV
6) Stages: 6 stages
7) Stage energy: 0.833kJ
8) Impulse voltage waveform parameter:
     a) Standard lightning impulse voltage full-wave: 1.2±30%μs /50±20%μs,
          Amplitude: ±3%, oscillation at peak value less than 5% of amplitude
     b) Standard switching impulse voltage wave: 250±20%μs /2500±60%μs;
     c) This two impulse voltage waveform parameter and deviation meet the requirement of GB311 and GB16927.
9) Minimum output voltage efficiency
    Standard lightning impulse voltage full-wave≥90% (No test object)
    Standard switching impulse voltage wave≥75% (Test object capacitance3000pF)
10) Synchronous range: stage voltage is between 10%~100% of rated voltage.
       Positive and negative polarity synchronous range: less than 20%.
11) Synchronous discharge out of control rate <2% (Within the range: 10%~100% of rated voltage )
12) Sparking range: 10%-100%Un
13) Minimum output voltage: ≥10% rated voltage.
14) Charging voltage instability <±1.0%
15) Deviation between charging voltage and reference voltage <±1.0%
16) Working time:
       When voltage above than 70% rated voltage, the systems can continuous working each 120s (charging and discharging).
       When the voltage is below 70% of rated voltage, the system the system can continuous working each 60s
       (charging and discharging).
17) Under Maximum charging voltage, minimum discharge time not less than 60s.

Principle Diagram: 

 

Where To Buy

Related Products

Related Researches