HIVG 700KV-35KJ Impulse Voltage Generator
Home > Systems > Impulse Generator > Impulse Generator > ≤800kV Range

HIVG 700KV-35KJ Impulse Voltage Generator

Lead time: 60 days

Mode: HIVG 700KV-35KJ

Related Standards: 
* IEC 60060-1-2010 High-voltage test techniques - Part 1: General definitions and test requirements
* IEC 60060-2-2010 High-voltage test techniques. Part 2: Measuring systems
* IEC 61083-1-2001 Instruments and software used for measurement in high-voltage impulse tests - Part 1: Requirements for instruments
* IEC 61083-2-1996 Digital recorders for measurements in high-voltage tests - Part 2: Evaluation of software
* ANSI/IEEE 4a-2001 Techniques of High-Voltage Testing
* ANSI/IEEE 376-1975 Measurement of Impulse Strength and Impulse Bandwidth
* ANSI/IEEE 1122-2007 Digit Recorders for Measurements in High-Voltage Impulse Tests
* ASTM D69-D2484 Electrical Insulation (Ⅰ)
* ASTM D2518-Latest Electrical Insulation (Ⅱ)

impulse voltage generator 700KV impulse voltage generator 700KV

impulse voltage generator 700KV impulse voltage generator 700KV

Technical Parameters: 
1) Rated Voltage: ±700kV (Maximum upgraded to 3000kV)
2) Rated stage voltage: ±100kV
3) Rated charging voltage: ±100kV
4) Rated energy: 35kJ (Maximum upgraded to 150kJ)
5) Each stage impulse capacitor: 1.0μF/100kV, 0.142uF/700kV
6) Stages: 7 stages (Maximum upgraded to 30stages)
7) Stage energy: 5.0kJ
8) Load range: 400pF – 3000pF (included the capacitance of impulse voltage divider.)
9) Impulse voltage waveform parameter:
a) Standard lightning impulse voltage full-wave: 1.2±30%μs /50±20%μs,
Amplitude: ±3%, oscillation at peak value less than 5% of amplitude
b) This two impulse voltage waveform parameter and deviation meet the requirement of GB311 and GB16927.
10) Minimum output voltage efficiency: Standard lightning impulse voltage full-wave≥90% (No test object)
11) Synchronous range: stage voltage is between 10%~100% of rated voltage.
Positive and negative polarity synchronous range: less than 20%.
12) Synchronous discharge out of control rate <2% (Within the range: 10%~100% of rated voltage )
13) Sparking range: 10%-100%Un
14) Minimum output voltage: ≥10% rated voltage.
15) Charging voltage instability <±1.0%
16) Deviation between charging voltage and reference voltage <±1.0%
17) Working time:
When voltage above than 80% rated voltage, the systems can continuous working.
When the voltage is below 80% of rated voltage, the system the system can interrupted working (charging and discharging).
18) Under Maximum charging voltage, minimum discharge time not less than 60s.

Principle Diagram: 