Charging Transformer
HCTT-240kV/0.25A Charging Transformer
Home > Systems > HVDC Test System > Charging Transformer

HCTT-240kV/0.25A Charging Transformer

Mode: HCTT-240kV/0.25A
Rated capacitance:60kVA
Rated voltage: Exciting winding voltage:400V      HV voltage:240kV
Rated current: Exciting winding current:150A        HV current:0.25A
Rated frequency:50Hz
No-load current:≤10%
Waveform deviation:≤5%
Measuring winding voltage ratio:1000/1
Over-current capability: 150% of rated current, 5 min, no thermal damage and winding distortion to test transformer’s winding.
Over-voltage capability: 110% UH, 1 min, no damage to test transformer’s insulation.
Insulation level: LV winding to ground 3kV/1min ; HV winding to ground 3kV/1min
Dielectric loss<0.4% Running time: 100%UH,100%IH  1 hour;  80%UH.80%IH   cont. running.
Temperature raise of test transformer winding≤65
Temperature raise of oil surface≤55K
Partial discharge level: ≤5Pc under rated voltage ≤3Pc under 80% of rated voltage

Principle Diagram: 

  