>600kVA Range
HCR 1000KVA-3KV Compensation Reactor
Home > Systems > AC Dielectric Test > Compensation Reactor > >600kVA Range

HCR 1000KVA-3KV Compensation Reactor

Lead time: 60 days

Mode: HCR 1000KVA-3KV
1) Structure: Iron shell, stationary type iron core
2) Rated capacitance: 1000kVar
3) Rated frequency: 50Hz, 60Hz, 100Hz, 120Hz
4) Single phase
5) Rated voltage: 3kV (Transformer set separate taps for 100Hz and 120Hz testing.)
6) Rated current: compensation current output: 30 - 333.3A                   
7) Degree of linearity: <±1%
8) Sound level:  <70dB                                    
9) Over-current capacity: the over-current will not cause thermal damage or winding distortion to the compensation reactor,when the reactor working under 120% In continuous 10 min.
10) Over-voltage capacity: the over-voltage will not cause any insulation damage of the compensation reactor when the reactor working under 110%UH 10 minutes.
11) Working time: working for 60 min under 100% rated voltage and current
12) Temperature raises ≤65K, oil surface temperature raise ≤55K,

HCR 1000KVA-3KV Compensation Reactor, AC Dielectric Test System HCR 1000KVA-3KV Compensation Reactor, AC Dielectric Test System

HCR 1000KVA-3KV Compensation Reactor, AC Dielectric Test System HCR 1000KVA-3KV Compensation Reactor, AC Dielectric Test System
Attention: 
1) The winding is mutistrand copper wire parallel wound, which reducing reactor winding eddy-current loss.
Copper wire density ≤2A/mm2
2) Partial discharge measurement: PD ≤3pC under 100% UH
Insulation level: all insulation, all terminal insulation withstand to ground 10kV/min, no abnormal discharge.
3) Structure: adjustable reactor iron coil pass through single phase motor, which realize stepless reactance regulation.
At the same time, we will equip moisture absorb and oil drain valve for the reactor.     

Principle Diagram: 

  