HCR 5x150KVA-6KV Compensation Reactor
Home > Systems > AC Dielectric Test > Compensation Reactor > >600kVA Range

HCR 5x150KVA-6KV Compensation Reactor

Lead time: 60 days

Mode: HCR 5x150KVA-6KV
1) Structure: Iron shell, stationary type iron core
2) Rated capacitance: 5x150kVar (Equip five grades: 150, 300, 450, 600, 750, output with bushing.)
3) Rated current: 25, 50, 75, 100, 125A
4) Rated frequency: 50Hz
5) Rated voltage: 6kV
6) Single phase
7) Degree of linearity: <±1%
8) Sound level: <70dB (measured in 4 meters distance)                                        
9) Over-current capacity: the over-current will not cause thermal damage or winding distortion to the compensation reactor, when the reactor working under 120% In continuous 10 min.
10) Over-voltage capacity: the over-voltage will not cause any insulation damage of the compensation reactor when the reactor working under 110%UH 10 min.
11) Temperature raise ≤65K, oil surface temperature raise ≤55K,

Attention: 
1) The winding is mutistrand copper wire parallel wound, which reducing reactor winding eddy-current loss.
Copper wire density ≤2.5A/mm2
2) Insulation level: all insulation, all terminal insulation withstand to ground 10kV/min, no abnormal discharge.
3) Structure: adjustable reactor iron coil pass through single phase motor, which realize stepless reactance regulation.
At the same time, we will equip moisture absorber and oil drain valve for the reactor.