>600kVA Range
HCR 26x210KVA-3KV Compensation Reactor, AC Dielectric Test System
Home > Systems > AC Dielectric Test > Compensation Reactor > >600kVA Range

HCR 6x210KVA-3KV Compensation Reactor

Lead time: 60 days

Mode: HCR 6x210KVA-3KV
1) Iron shell, Single phase, 50Hz
2) Cooling: ONAN
3) Rated voltage: 3KV
4) Rated capacity: 6*210KVA (with six position 210, 420, 630, 840, 1050, 1260, all taps are led out by bushing);
5) Rated current: 70A, 140A, 210A, 280A, 350A, 420A;
6) Compensation is parallel in front of test transformer as power supply compensation, reducing power supply capacity;
7) Over current ability: working for 300s under 120% rated current without and heat damage and distortion to reactor winding;
8) Over voltage ability: working for 60 s under 100% rated voltage; temperature rising of reactor winding is ≤65K; temperature rising of oil surface is ≤55K;
9) PD level: ≤5pC under 100% rated voltage
10) Insulation level: all insulation, reactor winding ends to ground insulation withstand is 10KV/min without abnormal discharge
phenomenon
11) Dimension: 1650mm*1200mm*1900mm
12) Weight: < 2600kg

HCR 6x210KVA-3KV Compensation Reactor HCR 6x210KVA-3KV Compensation Reactor

HCR 6x210KVA-3KV Compensation Reactor HCR 6x210KVA-3KV Compensation Reactor
Principle Diagram: 

  