>600kVA Range
HCR 6x500KVA-10KV Compensation Reactor
Home > Systems > AC Dielectric Test > Compensation Reactor > >600kVA Range

HCR 6x500KVA-10KV Compensation Reactor

Lead time: 60 days

Mode: HCR 6x500KVA-10KV
1) Structure: Iron shell, stationary type iron core
2) Rated capacitance: 500x6kVar (500, 1000, 1500, 2000, 2500, 3000six grade, output with bushing)
3) Rated current: 50, 100, 150, 200, 250, 300A
4) Rated frequency: 50Hz
5) Rated voltage: 10kV
6) Single phase
7) Degree of linearity: <±1%
8) Sound level: <70dB (measured in 4 meters distance)                                        
9) Over-current capacity: the over-current will not cause thermal damage or winding distortion to the compensation reactor,when the reactor working under 120% In continuous 10 min.
10) Overvoltage capacity: the overvoltage will not cause any insulation damage of the compensation reactor when the reactor working under 110%UH 10 min.
11) Working time: 5 min on, 30 min off, 20 cycles per day; Temperature rising is ≤65K, oil surface temperature rising is ≤55K.

HCR 6x500KVA-10KV Compensation Reactor, AC Dielectric Test System HCR 6x500KVA-10KV Compensation Reactor, AC Dielectric Test System

HCR 6x500KVA-10KV Compensation Reactor, AC Dielectric Test System HCR 6x500KVA-10KV Compensation Reactor, AC Dielectric Test System
Attention: 
1) The winding is mutistrand copper wire parallel wound, which reducing reactor winding eddy-current loss.
Copper wire density ≤2.5A/mm2
2) Insulation level: all insulation, all terminal insulation withstand to ground 10kV/min, no abnormal discharge.
3) Structure: adjustable reactor iron coil pass through single phase motor, which realize stepless reactance regulation.
At the same time, we will equip moisture absorber and oil drain valve for the reactor.