Mode: HCR 800KVA-0.6KV
1) Structure: Iron shell, stationary type iron core
2) Rated Capacitance: 800kVar
3) Rated Frequency: 60Hz
4) Single Phase
5) Rated Voltage: 0.6kV
6) Degree of Linearity: <±1%
7) Compensation Current: 100A~1333.5A
8) Sound Level: <70dB (measured in 4 meters distance)
9) Over-current Capacity: the over-current will not cause thermal damage or winding distortion to the compensation reactor, when the reactor working under 120% In continuous 10minutes.
10) Over-voltage Capacity: the overvoltage will not cause any insulation damage of the compensation reactor when the reactor working under 110%UH 60 minutes.
11) Working Time: working for 60 min under rated voltage and current
Attention:
1) The winding is mutistrand copper wire parallel wound, which reducing reactor winding eddy-current loss. Copper wire density ≤2A/mm2
2) Insulation level: all insulation, all terminal insulation withstand to ground 5kV/min, no abnormal discharge.
3) Structure: adjustable reactor iron coil pass through single phase motor, which realize stepless reactance regulation. At the same time, we will equip moisture absorb and oil drain valve for the reactor.
Principle Diagram:
HIMALAYAL provides innovative products that comprise high voltage test equipment, full-set high voltage test instruments, on-site test systems and on-line monitoring systems, and services regarding tests, diagnostics and asset monitoring for clients in power industry. We help to ensure safety and reliability in the power generation, transmission and distribution.
Himalayal Corporation Limited
Tel:+86 21 5059 9069
Email: info@himalayal.com
http://www.himalayal.com
http://www.himalayal.com.cn