HCR 4x100KVA-3KV Compensation Reactor
Home > Systems > AC Dielectric Test > Compensation Reactor > ≤600KVA Range

HCR 4x100KVA-3KV Compensation Reactor

Lead time: 45 days

Mode: HCR 4x100KVA-3KV
1) Single phase, 50Hz
2) Rated voltage: 3KV
3) Rated capacity: 4x100KVA (with 4 positions: 100, 200, 300, 400KVA, all bushing lead out exchange capacity by manual);
4) Rated current: 33.3A, 66.6A, 100A, 133.3A
5) Linearity: <± 1%
6) Noise: <70dB
7) Adjustment: manual adjustment
8) Over current ability: working for 5 min under 120% rated current without any heat damage and distortion to reactor winding;
9) Insulation level: all insulation, winding ends to ground insulation withstand is 5KV/ 1min without abnormal discharge phenomenon;
10) Over voltage ability: working for 60 min under 100% rated voltage; temperature rising of reactor winding is ≤65K; temperature of oil surface is ≤55K;
11) Structure: tank shell with adjustable iron core. On the oil tank installed measurable current transformer 375:5,and reactor conservator equipped with breather; oil drain valve on the bottom which is convenient to take oil sample.
12) Working time: working for 60 min under 100% rated voltage and current.