≤600KVA Range
HCR 6x100KVA-6KV Compensation Reactor
Home > Systems > AC Dielectric Test > Compensation Reactor > ≤600KVA Range

HCR 6x100KVA-6KV Compensation Reactor

Lead time: 45 days

Mode: HCR 6x100KVA-6KV
1) Structure: Iron shell, stationary type iron core
2) Rated capacitance: 6x100kVar (Six grade: 100, 200, 300, 400, 500, 600, out lead with bushing)
3) Rated frequency: 50Hz
4) Rated voltage: 6kV
5) Rated current: 16.6, 33.3, 50, 66.6, 83.3, 100A
6) Reactor equip compensation current transformer (400:5), install inside compensation reactor.
7) Single phase
8) Degree of linearity: <±1%
9) Sound level: <70dB  (measured in 4 meters distance)                                        
10) Over-current capacity: the over-current will not cause thermal damage or winding distortion to the compensation reactor,when the reactor working under 120% In continuous 10 min
11) Over-voltage capacity: the over-voltage will not cause any insulation damage of the compensation reactor when the reactor working under 110%UH 10 min.
12) Working time: continuous working for 30 min under 100% rated voltage; Temperature raise ≤65K, oil surface temperature raise ≤55K;

HCR 6x100KVA-6KV Compensation Reactor, AC Dielectric Test System HCR 6x100KVA-6KV Compensation Reactor, AC Dielectric Test System

HCR 6x100KVA-6KV Compensation Reactor, AC Dielectric Test System HCR 6x100KVA-6KV Compensation Reactor, AC Dielectric Test System
Attention: 
1) The winding is mutistrand copper wire parallel wound, which reducing reactor winding eddy-current loss.
Copper wire density ≤2.5A/mm2
2) Insulation level: all insulation, all terminal insulation withstand to ground 20kV/min, no abnormal discharge.
3) Structure: adjustable reactor iron coil pass through single phase motor, which realize stepless reactance regulation.
At the same time, we will equip moisture absorber and oil drain valve for the reactor.

Principle Diagram: 

  