100kVA ~ 400kVA Range
HET 150kVA/3.9kV,2.5kV,1.75kV Exciter Transformer
Home > Systems > Inductance Resonant > Exciting Transformer > 100kVA ~ 400kVA Range

HET 150kVA/3.9kV,2.5kV,1.75kV Exciter Transformer

Lead time: 30 days

Mode: HET 150kVA/3.9kV,2.5kV,1.75kV
Rated frequency: 20~300Hz
Rated capacitance: 150kVA
HV winding is independent winding
Rated LV voltage: 2x450V, 2x500V,2x550V
HV winding voltage: 1.75kV, 2.5kV, 3.9kV
Rated LV current: 2x150V
HV winding current: 38.5A
Rated frequency: 20-300Hz
Cooling methods: ONAN
Heat-resistance: A grade, 25# transformer oil
Working time: continuous working 60 min under rated output capacitance, winding≤65K, oil surface≤55K;
Sound level: 60dB Impedance level:≤5%
Structure requirement: oil immersed shell type, silicon steel plate is DQ130-30 high quality cooling rolling silicon steel plate, Bm value very low; Transformer has double coils, cooper lead wire, Low voltage winding and HV winding, adopt electrostatic shielding between two windings which has the function of isolation filter; equips measuring coil, used to measure HV side voltage; there are oil expansion tank and moister absorber on transformer; Oil temperature thermograph and oil level indicator are set on oil expansion tank; Transformer’s spare part and component, e.g. bushing, valve and oil conservator’s structure and layout will not affect the transportation. There are also enough safety distance between transformer HV and LV winding, will not cause partial discharge and corona when testing.

Principle Diagram: 

  