Mode: HFRS 130KV/10400KVA
Cooling: ONAN Rated voltage: 130KV
Rated current: 80A Rated capacity: 10400KVA
Rated inductance: 8H±1%
Insulation level: 1.1 times the rated voltage withstand 1min
Operating frequency: 20 ~ 300Hz Quality factor: Q> 70 ~ 120
Running time: continuous operation at rated capacity break down for 60min and then off for 60min, no more than 8 times a day, the coil temperature rise is less than 65K, transformer oil temperature is less than 55K.
Parameters of high voltage reactor: two stages in parallel connection:
Mode: HFRS 130/20800
Cooling: ONAN Rated voltage: 130KV
Rated current: 160A Rated capacity: 20800KVA
Rated inductance: 4H±1%
Insulation level: 1.1 times the rated voltage withstand 1min
Operating frequency: 20 ~ 300Hz Quality factor: Q> 70 ~ 120
Running time: continuous operation at rated capacity break down for 60min and then off for 60min, no more than 8 times a day, the coil temperature rise is less than 65K, transformer oil temperature is less than 55K.
Structure Requirement:
Using iron and copper winding segment gap structure, reactors using copper wire windings, oil-immersed self-cooled, fuel tank as iron shell structure in order to increase the cooling capacity of the windings and margin expansion and contraction, and equip with breathing capsules which is enough for the expansion of transformer oil.
Reactors have to equip with some fixed facilities to bear the weight of special lifting and transportation. Considering the internal structure of the reactor, it should be no loose after a normal rail and road transport and mutual position unchanged.
Reactor has a single piece of equipment nameplate parameters: Rated voltage, inductance, frequency, weight, etc.
High-voltage bushing using a voltage rating of GS-130kV / 300A plug-composite material made high voltage bushing. High voltage output ends have a corona anti-corona
Principle Diagram:
HIMALAYAL provides innovative products that comprise high voltage test equipment, full-set high voltage test instruments, on-site test systems and on-line monitoring systems, and services regarding tests, diagnostics and asset monitoring for clients in power industry. We help to ensure safety and reliability in the power generation, transmission and distribution.