Cylinder Type
HFRS 200kV/400KVA Variable Frequency Resonant Reactor, Frequency Resonant Reactor
Home > Systems > Frequency Resonant > Variable Frequency Resonant Reactor > Cylinder Type

HFRS 200kV/400KVA Variable Frequency Resonant Reactor

Lead time: 60 days

Mode: HFRS 200kV/400KVA
Single modules                                                  Rated capacitance: 400kVA
Rated voltage: 200kV                                        Rated current: 2A,     Operation frequency: 50~300Hz
Working time : Continue running 60min ,under 100%UH,100%IH
System quality factor (Q): Q≥50                      Rated inductance :318H
Partial discharge:with 100% rated voltage ,PD less than 10pC
Insulation level:withstand 220kV/1min         Noise level: ≤75dB

Structure Requirement: 
The system adopts iron coil subsection air gap and copper winding structure, reactor adopts cooling, oil tank is iron shell structure to increase the system heat dissipation capability, and equips with breathe capsule for transformer oil expanding when testing. Reactor equips reliable hook for suspending.
The inner structure of the reactor is special designed for long distance railway, highway transportation. The system suitable for on-site test.
Reactor has nameplate for single unit and serial connection: the parameter on nameplate are:Rated voltage, inductance, working frequency, weight, and so on.
Compared with Epoxy tube type structure, the Metal tank structure has better function on heat dissipation. And Tank structure has better performance on on-site testing.

Principle Diagram: 

  
Where To Buy