Cylinder Type
HFRS 260kV/10000kVA Variable Frequency Resonant Reactor,Frequency Resonant Reactor
Home > Systems > Frequency Resonant > Variable Frequency Resonant Reactor > Cylinder Type

HFRS 260kV/10000kVA Variable Frequency Resonant Reactor

Lead time: 120 days

Mode: HFRS 260kV/10000kVA
Rated voltage;260kV                      Rated current:38.5A
Rated capacitance;10000kVA       Rated inductance;30H±2%
Insulation level:1.1times rated voltage,1min
Rated frequency:25~300Hz           Quality factor:Q>65~120
Working time: Running time requirement: one hour on, one hour off, every day 3cycle.
Temperature raise: winding≤80K, transformer oil≤55K;

Structure Requirement: 
The system adopts iron coil subsection air gap and copper winding structure, reactor adopts copper lead-wire winding, oil immerse self-cooling, oil tank is iron shell structure to increase the system heat dissipation capability, and equips with breathe capsule for transformer oil expanding when testing. Reactor equips reliable hook for suspending.
The inner structure of the reactor is special designed for long distance railway, highway transportation. The system suitable for on-site test.
Reactor has nameplate for single unit and serial connection: the parameter on nameplate are: Rated voltage, inductance, working frequency, weight, and so on.
Compared with Epoxy tube type structure, the Metal tank structure has better function on heat dissipation. And Tank structure has better performance on on-site testing.

Principle Diagram: 

  