Mode: HFRS 600kV/2500kVA
Single phase Stage: three
Single stage rated capacitance: 833kVA
Two stage rated capacitance:1666kVA
Three stage rated capacitance:2500kVA
Single stage rated voltage: 200kV
Two stage rated voltage:400kV
Three stage rated voltage:600kV
Rated current: 4.16A Operation frequency: 50~300Hz
Working time : Continue running 60min ,under 100%UH,100%IH.
System quality factor (Q): Q≥50
Single-stage reactor inductance :120H
Two stage reactor inductance in series connection:240H
Three stage reactor inductance in series connection:360H
Noise level: ≤75dB
Structure Requirement:
The system adopts iron coil subsection air gap and copper winding structure, reactor adopts copper lead-wire winding, oil immerse self-cooling, oil tank is iron shell structure to increase the system heat dissipation capability, and equips with breathe capsule for transformer oil expanding when testing. Reactor equips reliable hook for suspending.
The inner structure of the reactor is special designed for long distance railway, highway transportation. The system suitable for on-site test.
Reactor has nameplate for single unit and serial connection: the parameter on nameplate are: Rated voltage, inductance, working frequency, weight, and so on.
Compared with Epoxy tube type structure, the Metal tank structure has better function on heat dissipation. And Tank structure has better performance on on-site testing.
Principle Diagram:
HIMALAYAL provides innovative products that comprise high voltage test equipment, full-set high voltage test instruments, on-site test systems and on-line monitoring systems, and services regarding tests, diagnostics and asset monitoring for clients in power industry. We help to ensure safety and reliability in the power generation, transmission and distribution.
Himalayal Corporation Limited
Tel:+86 21 5059 9069
Email: info@himalayal.com
http://www.himalayal.com
http://www.himalayal.com.cn