Tank Type
HFRS-T 200kV/10000kVAVariable Frequency Resonant Reactor,Frequency Resonant Reactor
Home > Systems > Frequency Resonant > Variable Frequency Resonant Reactor > Tank Type

HFRS-T 200kV/10000kVAVariable Frequency Resonant Reactor

Lead time: 120 days

Mode: HFRS-T 200kV/10000kVA
Single Module                                Rated voltage: 200kV
Rated current: 50A                        Rated capacitance: 10000kVA
Rated inductance: 20H±1%         Error: <1%
Insulation level: withstand 60s under 110% rated voltage
Rated frequency: 20~300Hz        Quality factor: Q>60 ~ 120
Working time: half hour one, one hour off, under rated output capacitance, not surpass 3cycles every day. Temperature raise: winding≤65K, transformer oil≤55K; Surface of epoxy tube temperature raise ≤40K

HFRS-T 2x200kV/20000kVA: 
Two reactors serial connection
Rated voltage: 400kV Rated current: 50A
Rated capacitance: 20000kVA Rated inductance: 40H±1%
Error: <1% Insulation level: withstand 60s under 110% rated voltage
Rated frequency: 20~300Hz Quality factor: Q>60 ~ 120
Working time: half hour one, one hour off, under rated output capacitance, not surpass 3 cycles every day. Temperature raise: winding≤65K,transformer oil≤55K; Surface of epoxy tube temperature raise ≤40K

Structure Requirement: 
There are two reactors, one reactor is supported by insulation support, which can withstand 200kV high voltage and equips necessary corona electrodes, to use when serial connection.
The system adopts iron coil subsection air gap and copper winding structure, reactor adopts copper lead-wire winding, oil immerse self-cooling, oil tank is iron shell structure to increase the system heat dissipation capability, and equips with breathe capsule for transformer oil expanding when testing. Reactor equips reliable hook for suspending.
The inner structure of the reactor is special designed for long distance railway, highway transportation. The system suitable for on-site testing.
Reactor has nameplate for single unit and serial connection: the parameter on nameplate are: Rated voltage, inductance, working frequency, weight, and so on.
Compared with Epoxy tube type structure, the Metal tank structure has better function on heat dissipation. And Tank structure has better performance on on-site testing.

Principle Diagram: 

 

  