Tank Type
HFRS-T 265kV/21995kVAVariable Frequency Resonant Reactor, Frequency Resonant Reactor
Home > Systems > Frequency Resonant > Variable Frequency Resonant Reactor > Tank Type

HFRS-T 265kV/21995kVAVariable Frequency Resonant Reactor

Lead time: 120 days

Mode: HFRS-T 265kV/21995kVA
Single Module                                                                Rated voltage: 265kV/169kV
Rated current: 83A/125A                                             Rated capacitance: 21995kVA
Rated inductance: 16.9H±2%/7.2H±2%                    Insulation level:286kV/1min;
Rated frequency: 30‐300Hz                                        Quality factor: Q>120(@30Hz)

Working time: one hour one, one hour off, under rated output capacitance, not surpass 3 cycle every day.
Temperature raise: winding≤65K, transformer oil≤55K; Surface of epoxy tube temperature raise ≤40K

Structure Requirement: 
The system adopts iron coil subsection air gap and copper winding structure, reactor adopts copper lead‐wire winding, oil immerse self‐cooling, oil tank is iron shell structure to increase the system heat dissipation capability, and equips with breathe capsule for
transformer oil expanding when testing. Reactor equips reliable hook for suspending.

The inner structure of the reactor is special designed for long distance trailway, highway transportation. The system suitable for on‐site test.
Reactor has nameplate for single unit and serial connection: the parameter on nameplate are: Rated voltage, inductance, working frequency, weight, and so on.
Compared with Epoxy tube type structure, the Metal tank structure has better function on heat dissipation. And Tank structure has better performance on on‐site testing.

Principle Diagram: 

 

  
Where To Buy

Related Researches