Tank Type
HFRS-T 300kV/51600kVAVariable Frequency Resonant Reactor, Frequency Resonant Reactor
Home > Systems > Frequency Resonant > Variable Frequency Resonant Reactor > Tank Type

HFRS-T 300kV/51600kVAVariable Frequency Resonant Reactor

Lead time: 120 days

Mode: HFRS-T 300kV/51600kVA
Two reactors                                           serial connection
Rated voltage: 300kV                             Rated current: 172A
Rated capacitance: 51600kVA               Rated inductance: 8.6H±1%
Error: <1%                                                Insulation level: withstand 60s under 110% rated voltage
Rated frequency: 25-400Hz                   Quality factor: Q>65 ~ 120

Working time: one hour one, one hour off, under rated output capacitance, not surpass 3 cycles every day. Temperature raise: winding≤80K, transformer oil≤55K; Surface of epoxy tube temperature raise ≤40K
Structure requirement:

There are two reactors, one reactor is supported by insulation support, which can withstand 150kV high voltage and equips necessary corona electrodes, to use when serial connection.
The system adopts iron coil subsection air gap and copper winding structure, reactor adopts copper lead-wire winding, oil immerse self-cooling, oil tank is iron shell structure to increase the system heat dissipation capability, and equips with breathe capsule for transformer oil expanding when testing. Reactor equips reliable hook for suspending.

The inner structure of the reactor is special designed for long distance railway, highway transportation. The system suitable for on-site testing.
Reactor has nameplate for single unit and serial connection: the parameter on nameplate are: Rated voltage, inductance, working frequency, weight, and so on.
Compared with Epoxy tube type structure, the Metal tank structure has better function on heat dissipation. And Tank structure has better performance on on-site testing.

Principle Diagram: 

 

  
Where To Buy

Related Researches