Gas Insulated Test Transformer
HGTS 1000KV/1600KVA Gas Insulated Test Transformer
Home > Systems > Gas Insulated System > Gas Insulated Test Transformer

HGTS 1000KV/1600KVA Gas Insulated Test Transformer

Lead time: 120 days

Mode: HGTS 1000KV/1600KVA
Casing, Stationary type                              Frequency: 50Hz
Single phase                                                Rated Capacity: 1600kVA
Rated Voltage: excitation winding: 3kV; HV winding: 1000kV
Rated Current: excitation current: 533.3A HV Current: 2A
(HV terminal of the transformer will be earthed through a current transformer 5/5 so as to check the current value of HV side and ensure safety of the operators and equipment)
Waveform deviation ≤3%                              Impedance voltage ≤10%
Unload Current: IO<10%                               Voltage Ratio of Measurement Windings: 1000:1

 
 

Over Current Ability: Continuous working for 300S under 120% rated current, then thermal damage or distortion of the winding shall not be occurred.
Over Voltage Ability: Overvoltage at 110% UH (880kV) for 60s, then it shall not happened any insulation damage for the testing transformer.
Insulation Level: 10kV/1min (low voltage input terminal to earth)
Partial discharge level: ≤3pC, under 100% rate voltage;     ≤2pC, under 80% rate voltage
Noise: ≤60dB                          Dielectric loss: <0.4%
Operating Time: Working for 60 minutes allowed at 100% rated current & voltage; Continuous working allowed at 80% rated current & voltage; and temperature rise of transformer windings is less than 40K.
Protection: Equip with 3kV surge arrestors.

Principle Diagram: 

  