Mode: HGTS 1200KV/3000KVA
Casing, Stationary type Frequency: 50Hz
Single phase Rated Capacity: 3000kVA
Rated Voltage: LV Voltage: 2x10kV; HV voltage: 1200kV
Rated Current: LV Current: 2x150A ; HV Current: 2.5A
Low voltage winding can be serial or parallel connected:
When serial connected: HV output is 600kV 2.5A;
When parallel connected: HV output is 1200kV 2.5A.
(HV terminal of the transformer will be earthed through a current transformer 5/5 so as to check the current value of HV side and ensure
safety of the operators and equipment)
Waveform deviation ≤3% Impedance voltage ≤18%
Over Current Ability: Continuous working for 300S under 120% rated current (3A), then thermal damage or distortion of the winding shall not be occurred.
Over Voltage Ability: Overvoltage at 110% UH (1260kV) for 60s, then it shall not happened any insulation damage for the testing transformer.
Insulation Level: 10kV/1min (low voltage input terminal to earth)
Partial discharge level: ≤3pC at 1000kV; ≤1pC at 800kV
Noise: ≤65dB Dielectric loss: <0.5%
Operating Time: at 1000kV 5000pF capacitance load, 5min on, 30min off; every day 20cycles.
Protection: Equip with 10kV surge arrestors.
Principle Diagram:
HIMALAYAL provides innovative products that comprise high voltage test equipment, full-set high voltage test instruments, on-site test systems and on-line monitoring systems, and services regarding tests, diagnostics and asset monitoring for clients in power industry. We help to ensure safety and reliability in the power generation, transmission and distribution.
Himalayal Corporation Limited
Tel:+86 21 5059 9069
Email: info@himalayal.com
http://www.himalayal.com
http://www.himalayal.com.cn