Gas Insulated Test Transformer
HGTS 325KV/100KVA Gas Insulated Test Transformer
Home > Systems > Gas Insulated System > Gas Insulated Test Transformer

HGTS 325KV/100KVA Gas Insulated Test Transformer

Lead time: 90 days

Mode: HGTS 325KV/100KVA
Casing, Stationary type               Single phase
Frequency: 50Hz                          Rated Capacity: 100kVA                                   
Rated Voltage: LV Voltage:  2x0.6kV;       HV winding: 325kV
Rated Current: LV current:  2x83.3A         HV Current: 0.31A

Low voltage winding can be serial or parallel connected: 
When serial connected, HV output is 162.5kV/0.31A
When parallel connected, HC output is 325kV/0.31A
(Test transformer HV terminal earth terminal earth via 5/5 CT, the HV side current can be supervised and guarantee the safety of operator.)
Waveform deviation <3%          Non-load Current: <10%             Impedance voltage <12%
Over Current Ability: Continuous working for 300S under 120% rated current (0.37A), then thermal damage or distortion of the winding shall not be occurred.
Over Voltage Ability: Overvoltage at 110% UH (357.5kV) for 60s, then it shall not happened any insulation damage for the testing transformer.
Partial discharge level: ≤5pC, under 100% rate voltage
Noise: ≤65dB             Dielectric loss: <0.5%       

Operating Time: 
Meet the requirement of 800pF load, test at 275kV, 15min on, 15min off, every day 8cycle;
2000pF load, test voltage 275kV, 2min on, 15min off, every day 8 cycle;
2000pF load, test voltage 145kV, 15min on, 15min off, every day 8 cycle.
Protection: Equip with 0.6kV surge arrestors at test transformer exciting winding.

Principle Diagram: 

  