Mode: HGTS 350KV/250KVA
Insulation cylinder, fixed type Gas insulated: SF6 gas insulated
Single phase, 50Hz Rated capacity: 250KVA
Rated voltage: low voltage: 2*0.6KV high voltage: 350KV
Rated current: lv current: 2*208.3A hv current: 0.714A
LV winding can be in both serial and parallel connection: in serial connection: hv output is 175kv/1A; in parallel connection, hv output is 350kv/2A
No load current: ≤10% Impedance voltage: ≤8.5% Waveform distortion: ≤3%
Over current ability: working for 1 min under 120% rated current without any heat damage and distortion to test transformer winding;
Over voltage ability: working for 1 min under 110% rated voltage, without any insulation damage to test transformer, at this moment, waveform distortion is ≤5%;
PD level: < 2pC under 100% rated voltage
Working time: working for 60 min under 100% rated voltage and current, temperature rising of transformer winding is ≤65K;
Protection: among transformer exciter installed 0.6KV MOA.
Principle Diagram:
HIMALAYAL provides innovative products that comprise high voltage test equipment, full-set high voltage test instruments, on-site test systems and on-line monitoring systems, and services regarding tests, diagnostics and asset monitoring for clients in power industry. We help to ensure safety and reliability in the power generation, transmission and distribution.