HVDC Control and measuring System
DCS-2010 Digital control and measuring system
Home > Systems > HVDC Test System > HVDC Control and measuring System

DCS-2010 Digital control and measuring system

Lead time: 30 days

1.Power supply unit

Power supply units is consist of insulation transformer, power conditioner, switching power supply. Insulation transformer can 

eliminate effect of electromagnetic interference generated by Impulse voltage test. Switching power supply feed the power of control device. 

2 .Main technical parameter and function

2.1 Control system technical parameter

DC voltage

Adjust accuracy: 1kV 

Instability of DC voltage: <3 % 

Dwell time

Setting range:      2s~4h

Adjust accuracy: 1s

Alarm delay:      1s 

2.2 Main function of control system 

Operation of test power supply switch.

Power supply voltage & current dial indicator and voltage regulator output voltage & current dial indicator.

Test object voltage & current dial indicator and applied measuring terminal, test object leakage current(1mA-10mA). There should be reliable electric insulation and protection between Current measuring terminal and main discharge circuit, 

which protect the control console from damaging. Measuring display of different polarity voltage current through polarity change circuit. 

Indicator light of voltage regulator raising & reducing voltage; Over-current, over-voltage auto-alarm; Alarm bell for raise voltage; Power supply lock, and the lock is control Desk. Fog room temperature display and measurement. 

Control console equip with over-voltage protection devices. We can protect the control units from damaging of test object flashover through suitable arrangement of wire and

 earthing. Control can realize the function of auto control HV discharge and display earthing signal.

Control console should can auto control earthing switch earthing, and display switch earthing signal.

Control console has the function of auto tripping when over-voltage happening.

Control console’s meters should can verification and self-check.

2.3  Main function of measuring system 

DC voltage; 400kV peak value;

2.4  Main characteristic

Control function stable and reliable.

System expansibility is excellent.

Easy operation, has operation prompt function

2.5  System basically configuration

All component are coming from excellent brand, reliable and safety.

2.6  Main function

Control and display

Integrate manual and automatic control function, automatic operating test procedure. 

Pre-set voltage polarity

Pre-set output voltage

Pre-set voltage applying time

Pre-set test procedure

Power supply switch operating

Voltage raising, reducing operation

Polarity reversing operation

Emergency trip operation

Emergency stop operation

Earthing switch operation

Display main circuit connection and equipment operation state

Display interface and parameter 

Manual or automatic control charging voltage

Automatic control charging procedure, adjust the charging voltage and time according to the test requirement; 

display charging voltage

Main power supply switchgear cabinet state (on / off)

Regulator contactor state (on / off)

Regulating motor contactor state (on / off)

Raising voltage dynamic display

Over-voltage and over-current early warming and protection

Display main circuit connection 

Record and printing of related parameter

Over-voltage, over-current early warming. 

2.7 Measuring display

Charging transformer primary voltage

Charging transformer primary current

DC charging voltage 

DC charging current

2.8 State display

Applied voltage time (Interface display)

Main power supply switchgear cabinet state (On/off)

Regulator, transformer contactor state (On/off)

Silicon stack reverse on positive/negative polarity

Each protection state

Earthing device state

Voltage polarity state

2.9 Protection and Interlock, connector

Over-current protection, auto alarm/pro.ection

Over-voltage protection, auto alarm/protection

Door interlock

Earthing switch interlock

Polarity reversing interlock

Voltage raising operation alarm

Alarm lamp, alarm bell and test area alarm function

Interlock and external alarm lamp, alarm bell extension connector

Principle Diagram: 

 

 

  
Where To Buy