1.Power supply unit
Power supply units is consist of insulation transformer, power conditioner, switching power supply. Insulation transformer can
eliminate effect of electromagnetic interference generated by Impulse voltage test. Switching power supply feed the power of control device.
2 .Main technical parameter and function
2.1 Control system technical parameter
DC voltage
Adjust accuracy: 1kV
Instability of DC voltage: <3 %
Dwell time
Setting range: 2s~4h
Adjust accuracy: 1s
Alarm delay: 1s
2.2 Main function of control system
Operation of test power supply switch.
Power supply voltage & current dial indicator and voltage regulator output voltage & current dial indicator.
Test object voltage & current dial indicator and applied measuring terminal, test object leakage current(1mA-10mA). There should be reliable electric insulation and protection between Current measuring terminal and main discharge circuit,
which protect the control console from damaging. Measuring display of different polarity voltage current through polarity change circuit.
Indicator light of voltage regulator raising & reducing voltage; Over-current, over-voltage auto-alarm; Alarm bell for raise voltage; Power supply lock, and the lock is control Desk. Fog room temperature display and measurement.
Control console equip with over-voltage protection devices. We can protect the control units from damaging of test object flashover through suitable arrangement of wire and
earthing. Control can realize the function of auto control HV discharge and display earthing signal.
Control console should can auto control earthing switch earthing, and display switch earthing signal.
Control console has the function of auto tripping when over-voltage happening.
Control console’s meters should can verification and self-check.
2.3 Main function of measuring system
DC voltage; 400kV peak value;
2.4 Main characteristic
Control function stable and reliable.
System expansibility is excellent.
Easy operation, has operation prompt function
2.5 System basically configuration
All component are coming from excellent brand, reliable and safety.
2.6 Main function
Control and display
Integrate manual and automatic control function, automatic operating test procedure.
Pre-set voltage polarity
Pre-set output voltage
Pre-set voltage applying time
Pre-set test procedure
Power supply switch operating
Voltage raising, reducing operation
Polarity reversing operation
Emergency trip operation
Emergency stop operation
Earthing switch operation
Display main circuit connection and equipment operation state
Display interface and parameter
Manual or automatic control charging voltage
Automatic control charging procedure, adjust the charging voltage and time according to the test requirement;
display charging voltage
Main power supply switchgear cabinet state (on / off)
Regulator contactor state (on / off)
Regulating motor contactor state (on / off)
Raising voltage dynamic display
Over-voltage and over-current early warming and protection
Display main circuit connection
Record and printing of related parameter
Over-voltage, over-current early warming.
2.7 Measuring display
Charging transformer primary voltage
Charging transformer primary current
DC charging voltage
DC charging current
2.8 State display
Applied voltage time (Interface display)
Main power supply switchgear cabinet state (On/off)
Regulator, transformer contactor state (On/off)
Silicon stack reverse on positive/negative polarity
Each protection state
Earthing device state
Voltage polarity state
2.9 Protection and Interlock, connector
Over-current protection, auto alarm/pro.ection
Over-voltage protection, auto alarm/protection
Door interlock
Earthing switch interlock
Polarity reversing interlock
Voltage raising operation alarm
Alarm lamp, alarm bell and test area alarm function
Interlock and external alarm lamp, alarm bell extension connector
Principle Diagram:
HIMALAYAL provides innovative products that comprise high voltage test equipment, full-set high voltage test instruments, on-site test systems and on-line monitoring systems, and services regarding tests, diagnostics and asset monitoring for clients in power industry. We help to ensure safety and reliability in the power generation, transmission and distribution.