HVF 1200kV/1500pF Coupling Capacitor & Capacitive Voltage Divider

Lead time: 45 days

Mode: HVF 1200kV/1500pF
Frequency: 60Hz                                                                              Nominal Dividing Ratio: 4000:1,
3stages                                                                                              Dielectric Loss <0.2%
Rated voltage: 1200kV (Stage voltage: 400kV)                           Cooling: ONAN
Rated capacity: 1500pF (Stage capacitance: 4500pF)              Measuring Accuracy: ≤±1%
Allowed Operating Time: same with the transformer
Insulation level: withstand 1min under 110% rated voltage (1320kV), no abnormal discharge phenomenon. Single stage withstand
480kV/1min.
Corona ring: aluminum alloy material, convenient for packing and transportation.
Pedestal: has enough stability, removable; voltage is measured via special measuring lead‐wire to variable frequency power source; can measure single stage and two stage serial connection voltage; HV connection adopts HV corona‐free connection, scalable.

HVF1200KV400pF Capacitor Voltage Divider HVF1200KV400pF Capacitor Voltage Divider

HVF1200KV400pF Capacitor Voltage Divider HVF1200KV400pF Capacitor Voltage Divider

Principle Diagram: 

  