Mode: HVF 500KV/500pF
Rated Voltage: 500kV Nominal Dividing Ratio: 2000:1
Frequency: 50Hz Dielectric Loss <0.5%
Capacitance: 500pF Temperature coefficient: <0.0005
Cooling: ONAN
PD Level: <5pC at rated voltage (500kV), <2pC at 80% of rated voltage (400kV)
Measuring Accuracy: ≤±1.5%
Allowed Operating Time: working for 60 min under 100% rated voltage and current
Connectors: two, one for HV output measurement to voltmeter, another for Partial Discharge Tester.
Dimension: φ250/φ1800×4500
Weight: <500kg
Principle Diagram:
HIMALAYAL provides innovative products that comprise high voltage test equipment, full-set high voltage test instruments, on-site test systems and on-line monitoring systems, and services regarding tests, diagnostics and asset monitoring for clients in power industry. We help to ensure safety and reliability in the power generation, transmission and distribution.
Himalayal Corporation Limited
Tel:+86 21 5059 9069
Email: info@himalayal.com
http://www.himalayal.com
http://www.himalayal.com.cn