800kV ~ 1600kV Range
HIVG 900KV-50.6KJ Impulse Voltage Generator
Home > Systems > Impulse Generator > Impulse Generator > 800kV ~ 1600kV Range

HIVG 900KV-50.6KJ Impulse Voltage Generator

Lead time: 75days

Mode: HIVG 900KV-50.6KJ

Related Standards: 
* IEC 60060-1-2010 High-voltage test techniques - Part 1: General definitions and test requirements
* IEC 60060-2-2010 High-voltage test techniques. Part 2: Measuring systems
* IEC 61083-1-2001 Instruments and software used for measurement in high-voltage impulse tests - Part 1: Requirements for instruments
* IEC 61083-2-1996 Digital recorders for measurements in high-voltage tests - Part 2: Evaluation of software
* ANSI/IEEE 4a-2001 Techniques of High-Voltage Testing
* ANSI/IEEE 376-1975 Measurement of Impulse Strength and Impulse Bandwidth
* ANSI/IEEE 1122-2007 Digit Recorders for Measurements in High-Voltage Impulse Tests
* ASTM D69-D2484 Electrical Insulation ()
* ASTM D2518-Latest Electrical Insulation (
)

impulse voltage generator 900KV impulse voltage generator 900KV

impulse voltage generator 900KV impulse voltage generator 900KV

Technical Parameters: 
1) Rated Voltage: ±900kV
2) Rated stage voltage: ±150kV
3) Rated charging voltage: 30kV ~ 150kV
4) Rated energy: 50.6kJ
5) Each stage impulse capacitor: 0.75μF/150kV, 0.125uF/900kV
6) Rated impulse capacity: 0.125μF
7) Stages: 6 stages
8) Impulse voltage waveform parameter:
     a) Standard lightning impulse voltage full-wave: 1.2±30%μs /50±20%μs,
         Amplitude: ±3%, oscillation at peak value less than 5% of amplitude
     b) Standard lightning chopping wave: TC ∈ [2μs,6μs], simulate artificial line time-delay mechanism, TC standard deviation less than 0.15uS
     c) This two impulse voltage waveform parameter and deviation meet the requirement of GB311 and GB16927.
9) Minimum output voltage efficiency Standard lightning impulse voltage full-wave≥90% (No test object)
10) Synchronous range: stage voltage is between 10%~100% of rated voltage.
       Positive and negative polarity synchronous range: less than 20%.
11) Synchronous discharge out of control rate <2% (Within the range: 10%~100% of rated voltage )
12) Sparking range: 10%-100%Un
13) Minimum output voltage: ≥10% rated voltage.
14) Charging voltage instability <±1.0%
15) Deviation between charging voltage and reference voltage <±1.0%
16) Working time:
       When voltage above than 70% rated voltage, the systems cancontinuous working each 120s (charging and discharging).
       When the voltage is below 70% of rated voltage, the system the system can continuous working each 60s (charging and discharging).
17) Under Maximum charging voltage, minimum discharge time not less than 60s.