Mode: HCRS 400kV/2000kVA
Cylinder type Single phase
Frequency :50Hz Cooling:ONAN
Stage :two Rated capacitance: 2000kVA
Single stage rated voltage: 400kV
Rated current: 5A;Max.Current:6A
Inductance adjusting range: 2535.6~184.4H
Load capacitance adjusting range: 4~55nF
Test object range:
375kV/17nF(Adopt reactor to increase voltage)
275kV/50nF(Adopt reactor to increase voltage)
15kV/350nF(Adopt 20kV tap of exciter transformer to increase voltage)
Over-current capability: working 300s under 120% IH (6A), no damage to reactor winding.
Over-voltage capability: working 60s under 110% UH(440kV), no damage to reactor insulation.
Output voltage waveform deviation: ≤1%
Working time and temperature: 60min under 100%UH, 100%IH,80%UH、80%IH which can continue running ,winding temperature raise not surpass 65K, oil temperature raise less than 55K.
System quality factor (Q): Q>50
Adjusting range for single-stage reactor inductance :5071~796H
Adjusting range for reactor inductance in series connection:10142~1592H
Adjusting range for single-stage load capacitance :2~12741pF
Adjusting range for load capacitance in series connection:1~6371pF
Noise level: ≤75dB (rated current)
Partial discharge level: <10pC under 100% rated voltage (400kV)
Structure: iron coil structure, user can change the reactance through adjusting open coil gaps, two epoxy tube, the steel bracket is made of stainless material in case of the reducing of quality factor which caused by eddy loss; pedestal has considered the heat which is caused by high-intensity magnetic field; the resonant system designation has considered the expand with heat and contract with cold of the oil.
- Internal structure:
①. 30-Q-130 Grain-Oriented Electrical Steel,
②. There are earthing baffle between winding and iron coil, the earthing is reliable.
③. We do many improment on the system; abandon some unreasonable structure and creat our new resonant. New variable inductance power frequency resonant reactor’s working life not less than 60 years.
④. The iron steel has been done the chip removing treatment. And then form a entirety with curing agent, which lower the noise; equip guide rail between adjustable iron coil and fixed iron coil, to make sure the iron coil move vertical or horizontal. We have been leader of the power frequency variable resonant system, moreover, we cooperate with famous university and research institute and improve ours quality continuously.
Principle Diagram:
HIMALAYAL provides innovative products that comprise high voltage test equipment, full-set high voltage test instruments, on-site test systems and on-line monitoring systems, and services regarding tests, diagnostics and asset monitoring for clients in power industry. We help to ensure safety and reliability in the power generation, transmission and distribution.