Cylinder Type
HCRS 500kV/1000kVAInductance Resonant Reactor
Home > Systems > Inductance Resonant > Inductance Resonant Reactor > Cylinder Type

HCRS 500kV/1000kVA Inductance Resonant Reactor

Lead time: 120 days

Mode: HCRS 500kV/1000kVA
Cylinder type Single phase
Rated capacitance: 1000kVA Rated voltage:500kV
Rated current: 2A, Maximum current: 2.4A
Partial discharge level: <2pC under 100% rated voltage,
Rated frequency: 50Hz Output voltage waveform deviation: ≤1.5%
Max. capacitance of test object: 4000~25483pF (single module)
2000~12741pF (Two modules serial connection)
Inductance adjusting range: 2535.6~398H (single module)
5071.2~796H (Two modules serial connection)
Reactance adjusting range: 796.2<Xl<125kΩ (single module)
1592.4<Xl<250kΩ (Two modules serial connection)
Over-current capability: working 300s under 125% IH (2.5A), no damage to reactor winding .
Over-voltage capability: working 60s under 110% UH(550kV), no damage to reactor insulation.
Working time and temperature: working 60min under rated load;  continuous working under 80% rated current and rated voltage; winding temperature raise not surpass 65K,  oil temperature raise less than 55K System quality factor (Q): Q≥50
Noise level: ≤75dB (under rated current)
Insulation level: 1 min under 110% rated voltage
Measuring system accuracy: 1grade
Input power: single phase, 4000V, rated frequency 50Hz,
Protection function: has the function of over-voltage, over-current and test object flashover protection; Reactor max. air gap and min. air gap protection.
Linearity: 10%-100% reactance, error≤±1%
Structure: iron coil structure, user can change the reactance through adjusting open coil gaps, two epoxy tube, the steel bracket is made of stainless material in case of the reducing of quality factor which caused by eddy loss; pedestal has considered the heat which is caused by high-intensity magnetic field; the resonant system designation has considered the expand with heat and contract with cold of the oil.
- Internal structure:
①. 30-Q-130 Grain-Oriented Electrical Steel,
②. There are earthing baffle between winding and iron coil, the earthing is reliable.
③. We do many improment on the system; abandon some unreasonable structure and creat our new resonant. New variable inductance power frequency resonant reactor’s working life not less than 60 years.
④. The iron steel has been done the chip removing treatment. And then form a entirety with curing agent, which lower the noise; equip guide rail between adjustable iron coil and fixed iron coil, to make sure the iron coil move vertical or horizontal. We have been leader of the power frequency variable resonant system, moreover, we cooperate with famous university and research institute and improve ours quality continuously.

Principle Diagram: 

  