Mode: HCRS 500kV/2000kVA
Cylinder type Single phase
Frequency: 50Hz Rated capacitance: 2000kVA
Rated voltage: 500kV (250kV/stage, two stages serial connection)
Maximum voltage: 550kV Rated current: 4A
Maximum current: 4.8A Partial discharge level: <2pC under 100% rated voltage
Rated frequency: 50Hz System quality factor > 40
Reactor quality factor > 50 Output voltage waveform deviation: ≤1.5%
Load capacitance:
Single unit reactor load range: 6nF – 50.9668nF
Two serial reactors load range: 3nF – 25.4834nF
System inductance: single unit minimum inductance 199H, maximum inductance 1690.4H; Two units minimum inductance 398H, maximum inductance 3380.8H
Over-current capability: working 600s under 110% IH, no damage to reactor winding .
Over-voltage capability: working 60s under 110% UH(550kV), no damage to reactor insulation.
System can be used under single unit or two modules serial connection.
We have successful supplied 2250kV 2A outdoor use test transformer, we can make sure the system external insulation can meet the test requirement under the condition of outdoor use (At 650kV, maximum voltage 700kV) . The below picture is one module of our 2250kV test transformer. Its dimension is 3500mm (Dia) * 7200mm (H), equips with epoxy skirt. System function will not be affected by raining, snow or else.
Structure: iron coil structure, user can change the reactance through adjusting open coil gaps, two epoxy tube, the steel bracket is made of stainless material in case of the reducing of quality factor which caused by eddy loss; pedestal has considered the heat which is caused by high-intensity magnetic field; the resonant system designation has considered the expand with heat and contract with cold of the oil.
Internal structure:
①. 30-Q-130 Grain-Oriented Electrical Steel,
②. There are earthing baffle between winding and iron coil, the earthing is reliable.
③. We do many improment on the system; abandon some unreasonable structure and creat our new resonant. New variable inductance power frequency resonant reactor’s working life not less than 60 years.
④. The iron steel has been done the chip removing treatment. And then form a entirety with curing agent, which lower the noise; equip guide rail between adjustable iron coil and fixed iron coil, to make sure the iron coil move vertical or horizontal. We have been leader of the power frequency variable resonant system, moreover, we cooperate with famous university and research institute and improve our quality continuously.
Principle Diagram:
HIMALAYAL provides innovative products that comprise high voltage test equipment, full-set high voltage test instruments, on-site test systems and on-line monitoring systems, and services regarding tests, diagnostics and asset monitoring for clients in power industry. We help to ensure safety and reliability in the power generation, transmission and distribution.