Tank Type
HTRS100kV/2000kVA(60kV) Inductance Resonant Reactor
Home > Systems > Inductance Resonant > Inductance Resonant Reactor > Tank Type

HTRS 100kV/2000kVA (60kV) Inductance Resonant Reactor

Lead time: 120 days

Mode: HTRS100kV/2000kVA(60kV)
Tank type  Single phase
Frequency: 50Hz  Indoor use
Rated Capacity: 2000kVA  Current adjusting range: 20A
Cooling methods: ONAN   Waveform deviation ≤1%
Noise:≤75dB             Quality factor: >30
Inductance adjusting range:

Technical parameter  Rated current  Inductance  Corresponding load  Inductance adjusting range
Rated voltage: 60KV  33.3A 4.78H  1.472uF  15:1  
Rated voltage100kV20A  13.26H  0.53uF  15:1  

Over Current Ability: Continuous working for 300S at110% rated current, then thermal damage or distortion of the winding shall not be occurred.
Over Voltage Ability: Overvoltage at 110% UH for 60s, then it shall not cause any insulation damage for the testing transformer.
PD Level :< 2pC at 100%UH of complete test system
Working time and temperature: one hour on and three hour off under rated load, everyday 3cycle.Winding temperature raise not surpass 65K, oil temperature raise less than 55K
Linearity: 10%-100% reactance, error≤±1%
Structure: iron coil structure, user can change the reactance through adjusting open coil gaps, two epoxy tube, the steel bracket is made of stainless material in case of the reducing of quality factor which caused by eddy loss; pedestal has considered the heat which is caused by high-intensity magnetic field; the resonant system designation has considered the expand with heat and contract with cold of the oil.
External structure:
Housing is tank type, and connected with flange at two terminals, resistant to impact, low leakage current and partial discharge, external color is sky blue.
Withstand 20kPa atmosphere sealing test, no leakage, no permanent deformation.
Sealing ring is acrylate material for aviations, oil resistance and thermo stability.
Transmission component structure:
Adopt good material, use 1Ni18T9 stainless steel, which can't transmit magnet, as guide rail.
In order to reduce the noise, adopt 1Ni18T9 stainless steel, which can't transmit magnet, double lead screw to drag the flexible iron coil.

HTRS 100kV/2000kVA Inductance Resonant HTRS 100kV/2000kVA Inductance Resonant

HTRS 100kV/2000kVA Inductance Resonant HTRS 100kV/2000kVA Inductance Resonant

Principle Diagram: 

  