Mode: HTRS120kV/3000kVA
Tank type Single phase
Frequency:50Hz Rated Capacity: 3000kVA
Rated input voltage: 0.415kV Rated output current: 25A
Rated output voltage: 120kV(Reactor equips 6kV Taps)
Rated current adjust range: 0.65A~25A
Rated load capacitance range: 0.0166~0.663μF
Rated reactance adjusting range: 611.5H~15.28H
Quality factor >40
Cooling methods: ONAN Waveform deviation ≤1%
Sound level: <70dB
PD Level <1pC at 100%UH of complete test system
Working time: under 100%UH,100%IH, One hour on, one hour off, 10 circle per day.Continuous working is allowed at 80UH, 80%IH; and temperature rise of transformer windings is less than 65K, temperature rise of oil surface is less than 55K, apperance temperature raise less than 30℃
Transformer Oil:25# China made
Structure Characteristic
Internal structure:
Use 30Q130 orientation silicon sheet, mitre equipped, head face is mopping and strapped with epoxy glass cloth
There are baffle between winding, iron coil and earth, reliable earthing.
Externl structure:
Tank type structure
The welding can bear 20kPa atmosphere pressure test, no lekage, no permanent deformation
Sealing ring is aeronautical material, oil resistance, high temperature resistance.
Principle Diagram:
HIMALAYAL provides innovative products that comprise high voltage test equipment, full-set high voltage test instruments, on-site test systems and on-line monitoring systems, and services regarding tests, diagnostics and asset monitoring for clients in power industry. We help to ensure safety and reliability in the power generation, transmission and distribution.
Himalayal Corporation Limited
Tel:+86 21 5059 9069
Email: info@himalayal.com