Tank Type
HTRS 20kV/2000kVA ,Inductance Resonant Reactor,Inductance Resonant System
Home > Systems > Inductance Resonant > Inductance Resonant Reactor > Tank Type

HTRS 20kV/2000kVA Inductance Resonant Reactor

Lead time: 90 days

Mode: HTRS 20kV/2000kVA
Tank type  Single phase
Frequency: 115Hz  Rated Capacity: 2000kVA
Rated output current: 100A  Rated output voltage: 20kV
Cooling methods: ONAN  Waveform deviation ≤1%
Quality factor: ≥40  Sound level: <70dB
Rated current adjust range: 5A~100A
Rated load capacitance range: 346.2nF~6924nF
Rated impedance adjusting range: 4kΩ~0.2kΩ
Rated reactance adjusting range: 5.538H~0.2769H
PD Level:<5pC at 100%UH of complete test system
Over-current capability: Working for 180s allowed at 120%In, not cause any damage to transformer winding and insulation.
Over-voltage capability: Working for 60s allowed at 110% (22kV)rated voltage, not cause any damage to transformer insulation.
Insulation level: withstand 5kV/min (Low voltage input ending to ground)
Working time: working 60 mintues under 100% rated voltage; Continuous working is allowed at 80% rated current & voltage; and temperature rise of transformer windings is less than 65K, temperature rise of oil surface is less than 55K.
Transformer Oil:25# China made
Structure: iron coil structure, user can change the reactance through adjusting open coil gaps, two epoxy tube, the steel bracket is made of stainless material in case of the reducing of quality factor which caused by eddy loss; pedestal has considered the heat which is caused by high‐intensity magnetic field; the resonant system designation has considered the expand with heat and contract with cold of the oil.
External structure:
① Housing is tank type, and connected with flange at two terminals, resistant to impact, low leakage current and partial discharge, external color is sky blue.
② Withstand 20kPa atmosphere sealing test, no leakage, no permanent deformation.
③ Sealing ring is acrylate material for aviations, oil resistance and thermo stability.
Transmission component structure:
①Adopt good material, use 1Ni18T9 stainless steel, which can't transmit magnet, as guide rail.
②In order to reduce the noise, adopt 1Ni18T9 stainless steel, which can't transmit magnet, double lead screw to drag the flexible iron coil.

Application: 
Cables/ Generators/ Power Factor Correction Capacitors/ Bushings/ CTs, PTs and CCVTs/ Partial Discharge Testing/ C & tan delta measuring

HTRS 20kV/2000kVA ,Inductance Resonant Reactor,Inductance Resonant System HTRS 20kV/2000kVA ,Inductance Resonant Reactor,Inductance Resonant System

HTRS 20kV/2000kVA ,Inductance Resonant Reactor,Inductance Resonant System HTRS 20kV/2000kVA ,Inductance Resonant Reactor,Inductance Resonant System
Principle Diagram: 

  
Where To Buy

Related produtcs

Related Photos

Related Researches