Current Limit Inductance
HIP 1000KV/0.5H Current Limit Inductance
Home > Systems > Inductance Resonant > Current Limit Inductance

HIP 1000KV/0.5H/10A Current Limit Inductance

Lead time: 50 days

Mode: HIP 1000KV/0.5H
1) The function of the impedance: prevent the damage of the reactor from the object breakdown.
Prevent the high frequency noise transfer from the HV end to the object end.
2) Frequency:50Hz
3) Rated voltage: 1000kV
4) Rated current: 10A
5) Rated inductance: 0.5H
6) Partial discharge level:
≤5pC, under 100% rate voltage
≤3pC, under 80% rate voltage
7) Temperature raise: continuous working under 100%IH, surface temperature raise not higher than 100K
8) Dimension: φ300×2000
9) Weight: <240kg

Principle Diagram: 

  