Current Limit Inductance
HIP 1000KV/0.1H Current Limit Inductance 
Home > Systems > Inductance Resonant > Current Limit Inductance

HIP 1000KV/0.1H/3A Current Limit Inductance 

Lead time: 50 days

Mode: HIP 1000KV/0.1H
1) The function of the impedance: prevent the damage of the reactor from the object breakdown.
Prevent the high frequency noise transfer from the HV end to the object end.
2) Nature cooling
3) Rated frequency: 30~300Hz
4) Rated voltage: 1000kV
5) Rated current: 3A
6) Rated inductance: 0.1H
7) Partial discharge level: <=10pC @ rated voltage, measure with the system
8) Temperature raise: continuous working 60min @ rated capacitance, surface temperature raise less than 80K.

Principle Diagram: 

  