Current Limit Inductance
HIP 200KV/0.04H Current Limit Inductance
Home > Systems > Inductance Resonant > Current Limit Inductance

HIP 200KV/0.04H Current Limit Inductance

Lead time: 30 days

Mode: HIP 200KV/0.04H
1) The function of the impedance: prevent the damage of the reactor from the object breakdown.
Prevent the high frequency noise transfer from the HV end to the object end.
2) Frequency: 50~300Hz
3) Rated voltage: 200kV
4) Rated current: 2A
5) Rated inductance: 0.04H
6) Cooling: ONAN
7) Temperature raise: 60min under 100%IH, inductance surface temperature raise not surpass 80K.