SF6 Gas Recovery Device & Charging Device
HCL/LH-19Y/18/180G SF6 Gas Recovery Device and Charging Device
Home > Instruments > Gas Treatment Device > SF6 Gas Recovery Device & Charging Device

HCL/LH-19Y/18/180G SF6 Gas Recovery Device and Charging Device

Lead time: 30 days

Mode: HCL/LH-19Y/18/180G SF6
This device is suitable for electricl equipment production use, and also used at110KV500KV GIS switchgear on-site installation and maintenance
 SF6 (Sulfur hexafluoride) Gas Recovery-Charging Device is the device used for recovery and disposal of SF6 gas when manufacturing, installing and maintaining SF6 electrical equipment. 

HCL/LH-19Y/18/180G SF6 Gas Recovery Device and Charging Device HCL/LH-19Y/18/180G SF6 Gas Recovery Device and Charging Device

HCL/LH-19Y/18/180G SF6 Gas Recovery Device and Charging Device HCL/LH-19Y/18/180G SF6 Gas Recovery Device and Charging Device

 SF6 Gas Recovery-Charging Device is possessed the following features: 
1. Adopting international advanced design principle of freezing liquefaction reduces working pressure of the system and greatly improves working efficiency of recovery.
2. Adopting column liquid level indicator, liquid level indication of SF6 is visual and accurate.
3. Equipped with digital display vacuum gauge.
4. Equipped with self-renewable dry filter.
5. Fill SF6 gas into steel cylinder.
6. Flow chart is drawn on operation panel, and it is easy to operate.
7. Adopting wind cooling, moveable mode, it can be used without water source.

Type  Freezing liquefaction, wind cooling, hand pushing  
Ambient temperature-10℃-40℃
Recycling   Initial pressure (Pa)  Freezing liquefaction, wind cooling, hand pushing
Final pressure (MPa)  ≦0.053  
Time required by 1m 3 cubage (h/m 3 )  ≦0.35
ChargingInitial pressure (Pa)≤133
Final pressure (MPa)0.7
Time required by 1m 3 cubage (h/m 3 )  ≤0.2  
Vacuum time from 0.1MPa to 133Pa ((h/m3)≤0.25
 Limit vacuum (Pa)  ≤10
Increase value of vacuum after 24 hrs from 133Pa (Pa)≤400
Annual leak rate  ≤0.5%  
Purity of SF6 gas after recovery  Water content (PPM/V)  ≤60  
Oil content (PPM/W)≤10  
Dust particle size≤1
Storage vessel Storage wayliquid state
Pressure(MPa)  3.9
volume(L)220
Amount of liquid(kg)  220
Liquefaction mode  Cooling liquefaction (without gaseous)
Gasification modeElectrical heating  
Renewing mode of dry filterRenewed by vacuum heating and activation
Power supplyThree phase  3Φ 380V  
Total power (kW)≤11  
NoisedB(A)≤75  
Dimension (mm)1970×1150×1700
Weight(kg)≤1200

   


Question 1: 
In Purification Drying System,the effect of oil separation is not good. How to solve it?
Answer:
The temperature of gas is likely to be high. To check whether the cooling fan runs normally and whether fan blades are in good condition.  If the oil separator is broken, please replace it.

Question 2:
In Purification Drying System, the drying effect is not good. How to solve it?
Answer:
It is possible that the molecular sieve saturation should be treated by self regeneration, or dry filter may be blocked. The system should be disassembled to replace inner parts if necessary. 