SF6 Gas Recovery Device & Charging Device
HCL/LH-19Y/18/350G SF6 Gas Recovery Device and Charging Device
Home > Instruments > Gas Treatment Device > SF6 Gas Recovery Device & Charging Device

HCL/LH-19Y/18/350G SF6 Gas Recovery Device and Charging Device

Lead time: 30 days

Mode: HCL/LH-19Y/18/350G
This device is suitable for electricl equipment production use, and also used at110KV500KV GIS switchgear on-site installation and maintenance

SF6 (Sulfur hexafluoride) Gas Recovery-Charging Device is the device used for recovery and disposal of SF6 gas when manufacturing, installing and maintaining SF6 

HCL/LH-19Y/18/350G SF6 Gas Recovery Device and Charging Device HCL/LH-19Y/18/350G SF6 Gas Recovery Device and Charging Device

HCL/LH-19Y/18/350G SF6 Gas Recovery Device and Charging Device HCL/LH-19Y/18/350G SF6 Gas Recovery Device and Charging Device


equipment. 
 SF6 Gas Recovery-Charging Device is possessed the following features: 
1. Adopting international advanced design principle of freezing liquefaction reduces working pressure of the system and 

greatly improves working efficiency of recovery.
2. Adopting column liquid level indicator, liquid level indication of SF6 is visual and accurate.
3. Equipped with digital display vacuum gauge.
4. Equipped with self-renewable dry filter.
5. Fill SF6 gas into steel cylinder.
6. Flow chart is drawn on operation panel, and it is easy to operate.
7. Adopting wind cooling, moveable mode, it can be used without water source.

Type

Freezing liquefaction, wind cooling, hand pushing

Ambient temperature

-10℃-40℃

Recycling 

Initial pressure (Pa)

Freezing liquefaction, wind cooling, hand pushing

Final pressure (MPa)

≦0.053

Time required by 1m 3 cubage (h/m 3 )

≦0.35

Charging

Initial pressure (Pa)

≤133

Final pressure (MPa)

0.7

Time required by 1m 3 cubage (h/m 3 )

≤0.2

Vacuum time from 0.1MPa to 133Pa ((h/m3)

≤0.25

 Limit vacuum (Pa)

≤10

Increase value of vacuum after 24 hrs from 133Pa (Pa)

≤400

Annual leak rate

≤0.5%

Purity of SF6 gas after recovery

Water content (PPM/V)

≤60

Oil content (PPM/W)

≤10

Dust particle size

≤1

Storage vessel 

Storage way

liquid state

Pressure(MPa)

3.9

volume(L)

390

Amount of liquid(kg)

390

Liquefaction mode

Cooling liquefaction (without gaseous)

Gasification mode

Electrical heating

Renewing mode of dry filter

Renewed by vacuum heating and activation

Power supply

Three phase  3Φ 380V

Total power (kW)

≤11

NoisedB(A)

≤75

Dimension (mm)

1970×1150×1700

Weight(kg)

≤1200

 


Question 1: 
The high pressure of refrigeration compressor is too high. What's the problem?
Answer:
Causes: Forget to turn on the cooling fan of condenser (or not running) or the condenser was choked up with pollutants.
Troubleshooting: Operate the fan; clean the condenser.

 

 